A problem has arisen within the industry concerning awareness of new renewable technologies and the requirement for the installer to ensure that all devices used for protection against electric shock are indeed appropriate for the purpose.
The main issue occurs when bi-directional power is possible and the requirement for devices that are suitable for bi-directional flow are fitted.
The amendment itself is very brief and has been brought in as an emergency regulation. This amendment can be downloaded from the IET website and should be used in conjunction with the current Regulations as the recognised standard.
The new Regulation number is 530.3.201 and simply states that “Selection and erection for protection shall take account of appropriate use of either a unidirectional device or a bidirectional device”
Notice that this is a “shall” Regulation and so, must be complied with!
It is worthy of note that manufactures must start to mark devices such as RCD’s RCBO’s and AFDD’s to indicate that they are unidirectional. This is generally accomplished by “in” and “out”; or with “line” and “load” arrows.
So, why has this change come about? There is a problem that can occur when power flows in both directions and we are relying on an RCD for additional protection. The RCD, in this case, is unlikely to trip which will result in a loss of additional protection under these circumstances. Further to this, if the RCD does trip for any other reason and power flows back, say from a PV array, the integrated circuit and solenoid which is used to open the contacts in the RCD, remain powered and can burn out. The user of the installation can then reset the RCD without the knowledge that it will not trip again, resulting in a loss of additional protection.
This does raise some questions as to which classification code should be issued when carrying out a condition report and there is a likelihood of bidirectional power flow. If the RCD is used as fault protection as in a TT system, then we face the prospect of earth faults going undetected. This becomes a loss of fault protection and so one could justify a C2 (potentially dangerous) classification code.
To summarize: A device suitable for bidirectional flow should be fitted when installing renewable technologies such as Battery storage systems, solar PV and V2G. This means “Vehicle to grid” which is a technology that allows the battery in the electric vehicle to be used as a power source.
The bidirectional RCD effectively has another pole included in the switching device. This prevents any power reaching the integrated circuit and solenoid when the RCD trips and will prevent any damage from occurring.
This will also comply with Regulation 341.1 (ii) “the effectiveness of the protective measures for safety during the intended life shall not diminish”
For further details of our City and Guilds 18th Edition courses visit City & Guilds 18th Edition Wiring Regulations Course | PTT (proactivetechnicaltraining.co.uk)